By: Nicole Imeson

With cooler weather comes one of the best and most common energy conservation measures (ECMs) in North America: free cooling, which uses outdoor conditions to reject heat without running a compressor. However, free cooling fails quietly, and when an economizer stops working, the compressor kicks in to pick up the load, masking failure from the building operators and occupants. Commissioning is the most reliable chance to catch failure before it becomes normal operation.

The two most common types are airside and waterside. ASHRAE 90.1, the Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings, mandates airside and waterside economizers in new buildings, additions, and HVAC alterations. Airside economizers require dampers that can supply 100% outdoor air, and waterside economizers require an economizer that can accommodate 100% of the expected load at 50°F dry-bulb/45°F wet-bulb and below. Many states reference 90.1 in their energy codes, and the NECB (National Energy Code of Canada for Buildings), adopted in most provinces, sets similar economizer requirements.

Airside Economization

Airside economizers come standard or optional on most rooftop units (RTUs) and air handling units (AHUs). When outdoor air is cooler than return air, the outdoor, return, and relief dampers modulate to bring in more outdoor air, meeting the supply air setpoint with little or no mechanical cooling. Economizer mode triggers on fixed dry-bulb, differential dry-bulb, fixed enthalpy, or differential enthalpy. Integrated units allow the economizer and compressor to run simultaneously while non-integrated units lock out the compressor when economizing.

Like any mechanical component that’s regularly changing state, these economizers are prone to failure. A 2004 study by Architectural Energy Corporation and the New Buildings Institute for the California Energy Commission’s Public Interest Energy Research (PIER) program, and associated 2003 PIER presentation, looked at 215 RTUs of 10 tons or smaller at 75 California sites. The researchers called small RTUs the “workhorses” of the commercial building industry, since they cool roughly 45% of US commercial floor space. They found 64% of economizers had failed, in line with other studies: 80% (PG&E, 2000), 66% (New England Electric System, 1993) and 65% (NEEA/PECI, 2003).

The PIER program study broke down the common failure modes amongst the 64% failure rate: sensor or control failures made up 46% of the failures, stuck or inoperable dampers 38%, and poor operation 16%. The researchers traced these to drifting sensors, leaky return dampers, incorrect field setup of economizer controllers, and incompatible economizers and thermostat controls. The PIER study put the average energy impact of a failed economizer at about 37% of annual cooling energy. 

To catch these hidden failures, ASHRAE 90.1 requires fault detection and diagnostics (FDD) on air-cooled DX units of 54,000 Btu/h and larger with economizers. The FDD system must report faults to operators, including air temperature sensor failure/fault, failure to economize, economizing when it shouldn’t, dampers not modulating, and excess outdoor air.

FDD adds one more system to functionally test. A thorough airside test checks outdoor, return, and mixed air sensors against a calibrated reference, strokes the dampers and confirms actual position against commanded position, steps through each changeover and integrated mode, and simulates faults to confirm the alarms reach operators. 

Waterside Economization

Waterside economizers use the same premise as airside, but instead of being integrated into a specific piece of equipment, they are added to a water-cooled chiller plant. In a standard plant, chilled water passes through the chiller, and the chiller compressors reject that heat to the condenser water loop, which flows outside to the cooling tower. When cooling tower water is cold enough, chilled water passes through a free-cooling plate-and-frame heat exchanger, rejecting heat directly to the condenser water loop, bypassing the chiller.

The cooling tower is open to the air, spraying condenser water through nozzles at the top of the cooling tower to flow down media and reject heat to the atmosphere before landing in the basin below. The heat exchanger keeps dust and debris out of the building’s chilled water loop. However, this can foul the heat exchanger, which is why designers often add a full-stream sediment separator and owners plan for annual cleaning.

Other common issues include failure or disabling of the controls that switch over from free to mechanical cooling, with some older buildings using a manual switchover process, leading to a lack of energy optimization and inconsistent chilled water temperatures, especially in places with large temperature swings over short periods of time, like in Calgary, AB. Trane's 2008 newsletter supports the point: “A poorly conceived automatic system during initiation of all-or-nothing free cooling will likely be disabled.”

A 2016 Trane newsletter noted that predicting whether a given day’s cooling load can be met with the waterside economizer is challenging because the tower’s approach to wet-bulb temperatures is inconsistent. Cold condenser water temperatures can cause chiller head pressure issues, although this issue isn’t limited to waterside economizers but is exacerbated by them. Year-round cooling demand requires freeze protection at cooling towers. Using an integrated mode to remain in economizer mode after the chiller starts “actually uses more energy than mechanical-only cooling.”

Although the failure modes are well documented, the quantity and frequency are not, making it hard to grasp the rate and cost of waterside economizer failure. By switching from mechanical to free cooling and back under real conditions, starting the chiller with cold condenser water to prove head pressure control, verifying tower freeze protection, and recording heat exchanger approach at turnover so operators have a baseline to spot fouling later, CxPs can test each failure mode.

Some plants opt for a free-cooling chiller instead of a heat exchanger. Internal valves facilitate refrigerant migration from the evaporator to the condenser, delivering roughly 45% to 60% of rated capacity with the compressors off. In addition to waterside’s tower risks, refrigerant economization valves sit inside the chiller, requiring the CxP to test them through the chiller controls and trends.

Testing in the Right Season

Because airside economizers have been field-tested, designers and code authorities are more aware of the risks and costs, leading to changes and fault-detection adoption in local codes. Even though waterside economizers share the same failure modes, no one has studied them, so data is scarce. Most economizers are only tested once, and often in the wrong season.

BCxA’s New Construction Commissioning (NCCx) Best Practices addresses this directly: “When thorough loading, staging, and capacities are not completed during the initial functional testing, testing is deferred to the appropriate season or load condition during occupancy” (section 4.4 C). Existing Building Commissioning (EBCx) section 3.13 carries the same principle: “Testing may need to be deferred based on climate conditions or occupancy.” NCCx also notes that testing dynamic sequences “is typically best performed in conjunction with, or followed by, the analysis of real-time data trends” (section 3.4 I.3). Testing free cooling in shoulder season, then monitoring it through variable conditions, catches the failures that are common in airside systems and that no one has measured in waterside systems.